Blog Technology suppport 2000W FIBER LASER CUTTING MACHINE SPECIAL CHILLER CWFL-2000 USER MANUAL

2000W FIBER LASER CUTTING MACHINE SPECIAL CHILLER CWFL-2000 USER MANUAL

June 27, 2021     Technology suppport

FIBER LASER CUTTING MACHINE SPECIAL CHILLER CWFL-2000 USER MANUAL

Contents

<1> Cautions ---------------------------------------------------------------- 3

<2> Contour and parts introduction ---------------------------------- 4

<3> Installation -------------------------------------------------------------- 5

<4> Operation and parameters adjustment ----------------------- 6

<5> Alarm and output terminal ----------------------------------------- 10

<6> Simple troubleshooting -------------------------------------------- 11

Thank you for using the machine from GUANGZHOU TEYUELECTROMECHANICAL CO., LTD.

Please read the installation instructionscarefully before installing and operating and keep it properly.

This installation instructions is not a quality assurance. GUANGZHOU TEYUELECTROMECHANICAL CO., LTD

reserves the right to the interpretation ofcorrection of typographical errors, improper mentioned information and

productimprovement. The amended content will be reprinted in installation instructionswithout notice in advance.

<1> Cautions

  1. Pleaseensure that the power supply and electrical outlet are in good contact and the earth wire must be firmly grounded!
  2. Please make sure there is stableand normal voltage for the working chiller! As the refrigeration compressor is
  3.  more sensitive to the power supply and voltage, so the operating voltage of our standard product is ±10%
  4. of the rated voltage. If you do need a wider operating voltage range, customization is available for us.
  5. Unmatchedpower frequency can cause the chiller damage!

Please choose model of 50Hz or 60Hz according to actual circumstance.

  1. Toprotect the pump, it’s strictly forbidden to run the chiller without water in the

storage water tank!

The new machine is packed after draining whole water in the tank, so please make sure the tank has water inside

before machine starting, otherwise it’s easily to have the pump damaged. When the water level is below the green

(NORMAL) range of the water level gauge, the cooling capacity of our chiller will go down slightly. Hence please

ensure the water level is within the green (NORMAL) range. To drain through circulating pump is strictly prohibited!

  1. Please besure that the air inlet and air outlet are in good ventilation! There must be at least 50cm from obstructions to the air outlet
  2.  which is in the back of the cooler, and should leave at least 30cm between obstructions and the side air inlet.
  3. The filter gauzemust be regularly cleaned!

It’s essential to remove and wash the dust gauze regularly, otherwise chiller malfunction can be caused by serious blockage.

  1. Please payattention to the effect of the condensate water!

With greater ambient humidity, when the water temperature is lower than theambient temperature, the condensate

water will generate on the surface ofwater circular pipes and the cooled components. If above circumstanceappears,

it is recommended to set a higher water temperature or keep pipesand cooled parts warm.

  1. Thisproduct is an industrial equipment. For professional use only.

<2> Contour and parts introduction

<3> Installation

It is very simple to install this industrial cooling machine. The installation for the

first time of the new machine can be carried out by following steps:

  1. Openthe package to check if the machine is intact and all the necessary

accessories are completed.

  1. Open the watersupply lid to feed cooling water.

Observing the water level gauge to feed water slowly, be careful not to have the

water overflowed!

  1. Accordingto system conditions, please connect the water inlet and outlet pipe

properly.

  1. Plugin power, turn on the power switch. (Do not start up without water in the

water tank!)

(1) Power switch turned on, the circulation pump of the chiller starts working. The

first time of operating may cause more bubbles in the pipe leading to a flow

alarming occasionally, but running for a few minutes later, it will go back to

normal.

(2) If the chiller starts for the first time, you must immediately check whether the

water pipe leaks.

(3) Power switched on, if the water temperature is under the set value, it is normal that fans and other components

of the machine do not work. The temperature controller will automatically control the working conditions of the

compressor, magnetic valve, fans and other parts based on the set controlling parameters.(4) As it takes a longer

time to start over the compressor and other components, according to different conditions,

the time is range from seconds to minutes, so do not turn on and off frequently.

  1. Checkthe water level in the water tank.

The first starting up of a new chiller will empty the air in the water pipe, causing a slight water level decline, but in

order to keep the water level in the green area, it is allowed to add adequate water again. Please observe and record the current water level, and inspect it again after the chiller running for a period of time, if the water level drops

obviously, please re-inspect the water pipeline leakage.

  1. Adjustparameters of temperature controller.

CWFL-2000 series use an intelligent thermostat. Normally users do not need toadjust the parameters. If it is necessary,

please refer to page 6 , “Operatingstatus and parameters adjustment.”

CWFL-2000 Series With 2000W Fiber Laser Cutting Machine

<4> Operation status and parameters

adjustment

The new T506 intelligent temperature controller does not need to adjust the

controlling parameters under normal circumstance. It will self-adjust

controlling parameters according to room temperature for meeting equipment

cooling requirements.

The new T506H intelligent temperature controller is selected constant

temperature control mode as factory setting with water temperature at 25℃.

User can adjust it as needed.

T506 and T506H controllers are of same functions and structure except

default setting.

  1. Temperaturecontrol panel introduction

   

(1). Indicators of temperature controller working status:

COMP                       ON, compressor working

SV                             ON, solenoid valve working

Heating                    ON, heating rod working

INT Ctrl                   ON, controller working in intelligent control mode

CT Ctrl                     ON, controller working in constant temperature control mode

PARAM Set           ON, controller working in parameters setting mode

ALM OUT             ON, alarm output status

Room Temp          ON, displaying room temperature

ST DLA                   ON, starting up delay status

(2). Press key to show the room temperature, 6 seconds later default display restored. (Meanwhile, Room Temp light is on, displaying room temperature.)

(3). keys are for modifying parameters values and keys are for switching parameter items. 6 CWFL-2000 Series

(4). RST key: confirm

(5). SET key: setting function

  1. Restore tofactory settings

Before machine startup, press and hold keys until the controller displays rE, 6 seconds later after releasing the keys, the controller works in normal order. All parameters values settings of the controller have been restored to factory settings.

  1. Alarmfunction

(1) Alarm Display:

When alarm occurs, the error code and the temperature will be alternately

displayed.

E1 E2 E3 E4 E5 E6
Ultrahigh room water temperature Ultrahigh water temperature Ultralowwater temperature Room temperature sensor failure Water temperature sensor failure Externalalarm input

(2) To suspend the alarm:

In alarming state, the alarm sound could be suspended by pressing any button,

but the alarm display remains until the alarm condition is eliminated.

  1. Temperaturecontroller parameters list
No Code Item Range T-506 Temperature controller Factory Setting T-506H Temperature controller Factory Setting Note
1 F0 Temperature setting F9~F8 30 25 Constant temperature control effecting
2 F1 Temperature Difference values -15~+5 -2 -2 Intelligent control
effecting
3 F2 Cooling hysteresis 0.1~3.0 0.3 0.3
4 F3 Way of control 0~1 1 0 1: intelligent
0: constant
temperature
5 F4 Alarm for ultrahigh
water temperature
1~20 20 10
6 F5 Alarm for ultralow
water temperature
1~20 20 15
7 F6 Alarm for ultrahigh
room temperature
40~50 45 45
8 F7 Password 00~99 8 8
9 F8F The allowed highest
water temperature
(F9+1) 35 30
10 F9 The allowed lowest
water temperature
~40
1 ~(F8-1)
25 20
  1. General settingsadjustment

Press SET key to enter into the user-defined state. Meanwhile, PARAM SET is on, controller in parameters setup status.

(1) Under intelligent mode, the control panel displays the temperature difference value between water and air (default value is -2).

(2) Under constant temperature mode , the control panel displays the set temperature value (default value is 25). At this moment, press keys to change settings. After modifying the value, press RST key to save and exit, then new parameters take effect, or press SET key to exit without saving parameters. If there is no more action within 20 seconds, it will automatically exit modifying status without saving parameters.

  1. Advancedsettings adjustment

(1) Press and hold the key while press SET key for 5 seconds until  displayed in upper window and PAS in lower window. Then press keys to select the password (default setting is 8), and then press the SET key, if the password is correct, F0 displays, entering into setup status, D1 flashing to indicate that the controller is under parameters setup status. If the password is incorrect, it returns to temperature display.

(2) Enter setup state, press keys to switch parameter items circularly, then press keys to modify the parameter values. Press enter key RST at any time to exit parameters setup with saving modified parameters and return to temperature display, then chiller runs under the new parameters. If no key is pressed within 20 seconds, the controller will automatically exit parameters setup without saving the modified parameters (under parameters setup status, system running in original parameters). Under parameters setup status, SET key does not work.

Note:

  1. Duringparameters setting condition, system runs under original parameters.
  2. Underconstant temperature control mode, the water temperature is controlled by parameter F0;
  1. Underintelligent control mode, the water temperature will be automatically adjusted according to temperature changes. The temperature difference is commanded by F1.

 

CWFL-2000 Series

  1. Advancedparameters adjustment cases:

No Code Item Value in case 1 Value in case 2 T-506H Temperature controller Factory Setting  T-506H
Temperature
controller
Factory Setting
1 F0 Temperature setting 28 20 30 25
2 F1 Temperature Difference values -2 -2
3 F2 Cooling hysteresis 2 1 0.3 0.3
4 F3 Way of control 0 0 1 0
5 F4 Alarm for ultrahigh
water temperature
5 4 20 10
6 F5 Alarm for ultralow
water temperature
10 14 20 15
7 F6 Alarm for ultrahigh
room temperature
45 48 48 45
8 F7 Password 8 8 8 8
9 F8F The allowed highest
water temperature
30 30 35 30
10 F9 The allowed lowest
water temperature
5 5 25 20

(1) Case 1: cooling water temperature is controlled by constant mode. Requiring water temperature is constant in 28℃, and the fluctuate does not exceed ±2℃. The alarm of over high water temperature will be on when water temperature is 5℃ higher than normal value, and the alarm of over low water temperature will be on when water temperature is 10 ℃ lower than normal value. It is convenient for user to adjust the water temperature between 5-30℃.

(2) Case 2: cooling water temperature is controlled by constant mode. Requiring water temperature is constant in 20℃, and the fluctuate does not exceed ±1℃. The over high water temperature will be on when water temperature is higher than 25℃, and the alarm of over low water temperature will be on when water temperature is lower than 5℃. (Regardless of what is the ambient temperature, the cooling water temperature is constant in 19℃ to 21℃)

<5> Alarm and output terminal

In order to guarantee the equipment will not be effected while abnormal situation happens on the chiller, CWFL-2000 dual temperature and dual pump series chillers possess alarm protection function.

  1. Alarmoutput terminals and wiring diagram.

  1. Alarmcauses and working status table.
Condition/Display Alarm code Buzzer Out H1.H2 Disconnection Out H1.H3 BREAK OVER
Circulating pump works
properly
DISCONNECTION BREAKOVER
Alarm of water shortage E6 Sounds BREAKOVER DISCONNECTION
Faulted circulating pump E6 Sounds BREAKOVER DISCONNECTION
Ultrahigh room temp E1 Sounds BREAKOVER DISCONNECTION
Ultrahigh water temp E2 Sounds BREAKOVER DISCONNECTION
Ultralow water temp E3 Sounds BREAKOVER DISCONNECTION
Faulted room temp sensor
(constant temp invalid)
E4 Sounds BREAKOVER DISCONNECTION
Faulted water temp sensor E5 Sounds BREAKOVER DISCONNECTION
Chiller power failure BREAKOVER DISCONNECTION

Note: The flow alarm is connected to the normally open relay and normally closed

relay contacts, requiring operating current less than 5A, working voltage less

than 300V.

<6> Simple troubleshooting

Failure Failure Cause Approach
Machine turned on but
unelectrified
Power cord is not plugged in place Check and ensure the power interface and the power plug is plugged in place and in good contact.
Fuse burnt-out Open the electric box cover, check the if necessary and check whether the
power supply voltage is stable; Check and ensure the power interface and the
power plug are in good contact.
Flow Alarm
(controller displays E6) use a water pipe directly connectto the water outlet and inlet but still without water   flowing
Water level in the storage water tank is too low Check the water level gauge display,add water until the level shown in the green area; And check whether water circulation pipe leaks.
Flow alarm occurs while
running with other
equipment (controller displays E6), but
there is water flowing and no
alarm when use a water pipe
directly connected to the
chiller water outlet and inlet.
Water circulation pipes are blocked or
a pipe bending deformation.
Check water circulation pipe
Ultra-high temperature alarm (controller displays E2) Blocked dust gauze, bad thermolysis Unpick and wash the dust gauze
regularly
Poor ventilation for air outlet and inlet To ensure a smooth ventilation
for air outlet and inlet
Voltage is extremely low or astable  To improve the power supply circuit or
use a voltage regulator
Improper parameter settings on To reset controlling parameters orrestore factory settings
thermostat Switch the power frequently To ensure there is sufficient time for refrigeration (more than 5 minuets)
Excessive heat load Reduce the heat load or use other
model with larger cooling capacity
Alarm for ultra-high room
temperature (controller displays E1)Serious problem of condensate water
The working ambient temperature is too high for the chiller Water temperature is much lower than ambient temperature, high humidity To improve the ventilation to guarantee that the machine is running under 40℃.Increase water temperature or to preserve heat for pipeline
Water drains slowly from
outfall during water changing
Injection port is not open Open the injection port

, , , , , ,